Configuration
46
3.1.3 Configuration Limits (Maximum Expansion)
The following configuration limits are valid for the A500:
distributed expansions (Modnet 1/SFB) for each programmable controller
BIK 151 / BIK 812 for I/O for each programmable controller 3
distributed expansions (DEA ... ) for each BIK 151 / BIK 812 16
distributed expansions (Modnet 1/SFB) for each A500 48 = 3 x 16
central expansions (PEAB) for each A500 and each programmable controller
controller set up with DTA 024 or DTA 028 9
controller set up with DTA 27.1 9
expansions (Modnet 1/SFB and PEAB) for each programmable controller
controller set up with DTA 024 or DTA 028 48 + 9
controller set up with DTA 27.1 48 + 9
controller set upt with DTA 101 or DTA 107 48 + 0
The maximum numbers for the I/O slots and for the I/O points cannot be derrived. The
following limits are valid for these:
Table 17 Configuration Limits of the A500
Configuration I/O Slots Binary I/O Points (max.)
9)
DTA 024 primary subrack 6
10)
192
DTA 027.1 primary subrack - -
DTA 028 primary subrack with DNP 028 10
10)
320
DTA 028 primary subrack with DNO 028 13
10)
416
DTA 101 primary subrack 4 128
DTA 025 secondary subrack 16 512
DTA 102/DTA 112 secondary subrack 4 128
DTA 103/DTA 113 secondary subrack 9 288
DTA 024 with max. I/O configuration via PEAB 149 = 9 x 16 + (6 - 1) 4768
DTA 27.1 with max. I/O configuration via PEAB 142 = 8 x 16 + 14 4544
DTA 028 with DNP 028 and max. I/O configuration via PEAB 153 = 9 x 16 + (10 - 1) 4896
DTA 028 with DNO 028 and max. I/O configuration via PEAB 156 = 9 x 16 + (13 - 1) 4992
max. /IO configuration via Modnet 1/SFB 159
11)
5088
max. I/O configuration via PEAB and Modnet 1/SFB 159 5088
Note The configuration for the maximum values resulting purely theoretically are not
obtained in practice by using intelligent function modules and analogue I/O modules.
9)
A
basis o
I
/
O modules with 32 I
/
O points is used. The given ma
x
imum value is reduced accordingly i
mod-
ules with fewer I/O points are used (analogue I/O, relay outputs, ...).
10) I
PE
A
B expansions are con
igured, an I
/
O slot must be reseerved in the primary subrack
or the DK
V
023.
11) Each DE
A
-H1 and each DE
A
-K1 “uses” 2 I
/
Oslots!