AEG SB4 series User Manual Page 412

  • Download
  • Add to my manuals
  • Print
  • Page
    / 431
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 411
23
UKA 024
365
Table 67 Setting the Value of the Voltage to be Monitored (on UKA 024)
SUE (2c04) BR 2 BR 1 BR 3 Limit
SUE0 (2c02)
24 VDC 18 VDC
48 VDC
34 VDC
60 VDC
44 VDC
The operation enable is executed if the supply and the voltage to be monitored for t
> 100 ms exceed the minimum value.
Acknowledgement (ACK key)
Error messages can be acknowledged with the ACK key (front panel) if the error is no
longer valid at the time of the acknowledgement. The length of the acknowledgement
signal is the same as the time while the key is pressed.
3.4 Graphical Symbols
Ready for service
Vchk
cycl
V
V
>70
o
C
B2, B4
PEAB
PMB
PD
break
2c 2
SUE 0
SUE 24
Bext
Mext
2c 4
2c 30
2c 32
2c 10
2c 12
2c 20
2c 22
2c 24
4/1
4/2
4/3
4/4
4/7
4/8
4/10
4/19
4/13
4/14
4/12
4/16
4 / 21, 24
E1
MPD 1
MPD 2
MPS 2
0V
MS
MPSA
MPSE
MPSE0
20 mA
20 mA
LSQ0
ACK
UKA 024
MPSA0
KE
KA
bat
bat
Figure 187 Graphical Symbol for UKA 024
3.5 Plug-In Check
Output 2c12 (KA) outputs a 12 V signal which is looped via all the I/O modules of the
controller. The loop is closed at 2c10 (KE) of the UKA. An interrupted loop is evaluated
(marker 20). If a signal check loop is not to be connected, 2c10 is to be jumpered with
2c12.
3.6 PEAB Monitoring
The perfect condition of the PEAB is monitored and signalled by saving and rewriting
PEAB signals. The following figure shows the hardware prerequisites for a system
Page view 411