Earthing and EMC-Measures
93
K1 Contact, e.g., for protective
logic and safety interlocks
V1 Safety diode in the
output module
V2 Clamping diode on site
Us
M
M
V1
V2
K1
Figure 62 Wiring Inductive Contact Elements
Inductive AC actuators are to be wired directly at the inductivity, e.g., with interference
suppression capacitors (RC elements) for the same reasons (see also Fig. Figure 36).
5.4.2 Wiring the Reference Conductor in an I solated Structure
If the reference conductors of the process periphery are not earthed against the recom-
mendation, e.g., as a safety measure, the corresponding reference conductors should
be wired as follows to improve the noise immunity:
Reference conductor
Functional earth
1M
0.1
μF
400 V-
Figure 63 Wiring the Reference Conductor in an Isolated Structure
The1M resistor discharges the static charges
The membrane capacitor (note the radio frequency input) short-circuits radio fre-
quency interference
A piece of earth fault monitoring equipment can be used to monitor the earth fault of
the U
S
working voltage:
Reference conductor (M)
Functional earth (PE)
1M
0.1
μF
400 VDC
Supply voltage to be monitored (Us 24)
220 VAC
H1
U
H1 Isolation monitoring equipment, e.g., RELNG1
Figure 64 Monitoring the Us Working Voltage for an Earth Fault
If the configuration covers several cabinets, the wiring is to be repeated for each cabi-
net.