10.3 TYPE RANGE 690 VOLT
TYPE VOLTAGE 690 VOLTS
TYPE CURRENT TYPE POWER DISSIPA- DIMENSIONS WEIGHT DIM. TEMP. CURRENT BURDEN SEMICON-
(A) (KVA) TION (MM)
(NET ABOUT
DRAW. CHARACTE- TRANSF. RESISTOR DUCTOR FUSE*
(W) W H D
KG)
(NO.) RISTIC (NO.) T1 R40 (Ω) F1 (A)
THYRO-P 1P
80 H 55 125 200 320 229 8 263 1 100/1 1.20 100
200 HF 138 260 200 370 229 9 265 2 200/1 1.00 250
300 HF 207 360 175 412 340 15 266 3 300/1 1.00 350
500 HF 345 625 175 412 340 15 266 3 500/1 1.00 630
780 HF 538 910 242 762 505 35 268 4 1000/1 1.20 2x630
1400 HF 966 1900 242 762 505 35 268 5 1500/1 1.00 4x700
2000 HF 1380 3200 521 577 445 62 270 6 2000/1 1.00 4x900
2600 HF 1794 3450 603 577 470 62 271 7 3000/1 1.10 4x1400
THYRO-P 2P
80 H 35 225 325 320 229 12 275 1 100/1 1.20 100
200 HF 239 485 325 404 229 15 277 2 200/1 1.00 250
300 HF 358 640 261 502 340 22 278 3 300/1 1.00 350
500 HF 597 1225 261 502 340 22 278 3 500/1 1.00 630
780 HF 932 1700 410 762 505 54 280 4 1000/1 1.20 2x630
1400 HF 1673 3750 410 762 505 54 280 5 1500/1 1.00 4x700
1850 HF 2210 5700 526 837 445 84 282 6 2000/1 1.00 4x900
2400 HF 2868 6400 603 837 470 107 283 7 3000/1 1.20 4x1400
THYRO-P 3P
80 H 95 350 450 320 229 17 287 1 100/1 1.20 100
200 HF 239 740 450 404 229 20 289 2 200/1 1.00 250
300 HF 358 1020 348 527 340 30 290 3 300/1 1.00 350
500 HF 597 1825 348 527 340 30 290 3 500/1 1.00 630
780 HF 932 2740 575 762 505 74 292 4 1000/1 1.20 2x630
1400 HF 1673 5600 575 762 505 74 292 5 1500/1 1.00 4x700
1700 HF 2031 8000 526 1094 445 119 294 6 2000/1 1.10 4x900
2200 HF 2619 9000 603 1094 470 152 295 7 3000/1 1.30 4x1400
THYRO-P 1P...VSC2
80 H 55 125 325 320 229 12 275 1 100/1 1.2 100
200 HF 138 260 325 397 229 15 277 2 200/1 1 250
300 HF 207 360 261 414 340 22 278 3 300/1 1 350
500 HF 345 625 261 414 340 22 3 500/1 1 630
780 HF 538 910 410 685 505 54 280 4 1000/1 1.2 2 x 630
1400 HF 966 1900 410 685 505 54 5 1500/1 1 4 x 700
1850 HF 1380 3200 526 837 445 84 282 6 2000/1 1 4 x 900
2400 HF 1794 3450 603 837 470 107 283 7 3000/1 1.1 4 x 1400
THYRO-P 1P...VSC3
80 H 55 125 450 320 229 17 287 1 100/1 1.2 100
200 HF 138 260 450 397 229 20 289 2 200/1 1 250
300 HF 207 360 348 430 340 30 290 3 300/1 1 350
500 HF 345 625 348 430 340 30 3 500/1 1 630
780 HF 538 910 575 685 505 74 292 4 1000/1 1.2 2 x 630
1400 HF 966 1900 575 685 505 74 5 1500/1 1 4 x 700
1700 HF 1380 3200 526 1094 445 119 294 6 2000/1 1 4 x 900
2200 HF 1794 3450 603 1094 470 152 295 7 3000/1 1.1 4 x 1400
* number of fuses per path of power section, built in