AEG NM 1600 Installation Manual Page 24

  • Download
  • Add to my manuals
  • Print
  • Page
    / 33
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 23
5. Technical Data
5.1. Technical Data
Nomen-
cla-
ture
1)
Parameter
Protect PV
10 kW
Protect PV
12.5 kW
Protect PV
15 kW
AC
P
ac,r
Max./Nom. power AC 10000 W 12500 W 15000 W
Reactive power range
0-6.0 kVA
r
0-7.5 kVA
r
0-9.0 kVA
r
V
ac,r
AC voltage range (P-N) 3x230 V ± 20 % 3x230 V ± 20 % 3x230 V ± 20 %
Nominal current AC 3 x 15 A 3 x 19 A 3 x 22 A
I
acmax
Max. current AC 3 x 15 A 3 x 19 A 3 x 22 A
AC current distortion (THD
%)
< 5 % < 5 % < 5 %
cosphi
ac,r
Power factor at 100 % load 0.99 0.99 0.99
Controlled power
factor range
0.8 over-excited
0.8 under-excited
0.8 over-excited
0.8 under-excited
0.8 over-excited
0.8 under-excited
“Connecting” power loss 10 W 10 W 10 W
Night-time power loss (off
grid)
< 5 W < 5 W < 5 W
f
r
Grid frequency 50 ± 5 Hz 50 ± 5 Hz 50 ± 5 Hz
DC
Nominal power DC 10300 W 12900 W 15500 W
Max. recommended PV
power at STC
2)
11800 Wp 14700 Wp 17700 Wp
V
dc,r
Nominal voltage DC 700 V 700 V 700 V
V
mppmin
-
V
mppmax
MPP voltage - nominal
power
3)
430-800 V 358-800 V 430-800 V
MPP efficiency 99.9 % 99.9 % 99.9 %
V
dcmax
Max. DC voltage 1000 V 1000 V 1000 V
V
dcstart
Turn on voltage DC 250 V 250 V 250 V
V
dcmin
Turn off voltage DC 250 V 250 V 250 V
I
dcmax
Max. current DC 2x12 A 3x12 A 3x12 A
Max. short circuit current
DC at STC
2x12 A 3x12 A 3x12 A
Min. on grid power 20 W 20 W 20 W
Efficiency
Max. efficiency 98 % 98 % 98 %
Euro efficiency, V at
dc,r
97.0 % 97.3 % 97.4 %
Other
Dimensions (L,W,H) 700x525x250 mm 700x525x250 mm 700x525x250 mm
Mounting recommendation Wall bracket Wall bracket Wall bracket
Weight 35 kg 35 kg 35 kg
Acoustic noise level
4
56 dB(A) 56 dB(A) 56 dB(A)
MPP trackers 2 3 3
Operation temperature
range
-25..60 °C -25..60 °C -25..60 °C
Nom. temperature range -25..45 °C -25..45 °C -25..45 °C
Storage temperature -25..60 °C -25..60 °C -25..60 °C
Overload operation Change of operat-
ing point
Change of operat-
ing point
Change of operat-
ing point
Overvoltage category AC Class III Class III Class III
Overvoltage category DC Class II Class II Class II
PLA Included Included Included
Reactive power Protect PV and
Protect PV easy
Protect PV and
Protect PV easy
Protect PV and
Protect PV easy
Functional Safety
Islanding detection - loss of
mains
Three-phase moni-
toring (ROCOF)
Three-phase moni-
toring (ROCOF)
Three-phase moni-
toring (ROCOF)
Voltage magnitude Included Included Included
Frequency Included Included Included
DC content of AC current Included Included Included
Insulation resistance Included Included Included
RCMU - Type B Included Included Included
Indirect contact protection Yes (class I, groun-
ded)
Yes (class I, groun-
ded)
Yes (class I, groun-
ded)
Short circuit protection Yes Yes Yes
Table 5.1: Specifications
5. Technical Data
8000038781_00_BAL_en / L00410564-01_02 23
5
Page view 23
1 2 ... 19 20 21 22 23 24 25 26 27 28 29 ... 32 33

Comments to this Manuals

No comments