Note:
If the two country selections do not match they will be cancelled and it will be necessary to
redo the selections. If a wrong country is accidentally accepted at the first selection, simply
accept the “Country: Undefined” in the confirm country screen. This will cancel the country
selection and a new selection is possible. If a wrong country is selected twice, call service.
The inverter will start automatically if sufficient solar radiation is available. The start-up will take
a few minutes. During this period, the inverter will carry out a self-test.
Actual Configuration
“Installed PV power”
to be
programmed
PV1, PV2 and PV3 are all set into individual mode. The nominal PV power
installed are:
PV 1: 6000 W PV 1: 6000 W
PV 2: 6000 W PV 2: 6000 W
PV 3: 3000 W PV 3: 3000 W
PV1 and PV2 are set into parallel mode and have a total of 10 kW PV
power installed. PV3 is set into individual mode and has nominal 4 kW PV
power.
PV 1: 5000 W
PV 2: 5000 W
PV 3: 4000 W
PV1 and PV2 are set into parallel mode and have a total of 11 kW PV
power installed. PV3 is set to ‘Off’ and has no PV installed.
PV 1: 5500 W
PV 2: 5500 W
PV 3: 0 W
Table 4.1: Examples of Installed PV Power
Note:
To meet medium voltage grid requirements, select a country option ending in (MV).
4.2.
Troubleshooting
For information on Troubleshooting, please see the Protect PV Reference Manual.
4.3.
Master Mode
The inverters include a Master Mode feature that allows one inverter to be appointed as Master
Inverter. From the Master Inverter’s web interface it is possible to access any inverter in the
network from one single point using a standard web browser. The Master Inverter can act as a
datalogger, collecting data from all inverters in the network. These data can be displayed
graphically from the Master Inverter’s own web server or can also be uploaded to external web-
portals or exported directly to a PC. The Master Inverter is also able to replicate settings and
data to the other inverters in the network, enabling easy commissioning and data management
4. Start-up and Check of Settings
8000038781_00_BAL_en / L00410564-01_02 21
4