C.1.4 Trouble-shooting
Here, the most frequent faults are listed which occur during the first commissioning
and permanent operation:
DIL switch no. 8 is set to ON or the rotary switch is to a position >3. If this is the
case, then the PCS enters a diagnosis routine after powering up. This is only
required for test purposes. Remedy: set DIL switch 8 to OFF or the rotary switch
to 0 and restart the PCS (by cycling power or pressing the momentary reset
push-button above the DIL switch).
A time-out is reported in the programmable controller. In this case, the fault is
to be searched at the programmable controller - PCS connection. Maybe, the
cable is defective or plugged in incorrectly. Maybe, a wrong driver is also loaded
in the PCS. An incorrectly defined flag word area is also possible.
Warning!
Check the action/reaction of the programmable controller!
After restarting the programmable controller following a communication loss,
the desired programmable controller reaction/action is to be examined to
avoid malfunctions.
The communication is active (PCS ERR LED is deactivated) but after a certain
time the following message appears on the upper display line of the PCS:
COMMUNICATION ERROR
An explanatory help text is shown on the lower display line:
TIMEOUT COMMUNICATION:
Transfer fault in the MODBUS 1 protocol. In this case, the PCS - programmable
controller connection is routed in a noisy environment, the cable length is too
long or the grounding is insufficient. Also, this message can result from a too
small or incorrectly defined flag word area in the programmable controller.
TIMEOUT PLC:
The determined time-out time (AA driver variable) was exceeded. This can occur
only in the SYNC operating mode and means that the synchronization word
(data word 3) was not processed in the programmable controller in time. Has
the handling software been loaded into the programmable controller? Is the
data area selected correctly? Is the restart input on 1 level?
A helpful diagnosis for the PCS 090/095/900 is the output of the PCS status on the
display. This display can be accessed by the following combination: press the
Help key after a PCS start (e.g. after a reset). The ERR LED must light constantly.
This option is available no more after starting the communication (ERR LED is
deactivated or flashes). By pressing the Help plus arrow keys you can display the
PCS version, the data block version, and the driver version as well as the selected
driver variables.