Protect PV.500 Operating Instructions
80000041664 BAL 41 of 73
The inverter is designed for a rated output power (sustained pow-
er) of 510 kW, see the technical data sheet. However, at low sup-
ply air temperatures, the inverter is capable of feeding in a higher
power. When the function is activated, the maximum feed-in ca-
pacity at low supply air temperatures is increased according to a
characteristic curve. If the temperature rises, the maximum feed-in
capacity drops. If the temperature rises above a certain value, the
device can only continue outputting the rated output power. The
relationship between the possible feed-in capacity and the temper-
ature is shown in Figure 13a.
Figure 13 a Extended operating mode
5.6.1 Parameters of the “Extended” operating mode
Temperature value at which the rated output power can be
fed:
If the supply air temperature rises above this value, it is only pos-
sible to continue feeding the rated output power.
Temperature value at which the maximum excess power can
be fed:
If the supply air temperature drops below this value, it is possible
to output the maximum excess power.
Power rating for normal feed-in capacity:
If the supply air temperature rises above the value, it is possible to
feed this power as the maximum. This value corresponds to the
rated output power.
Power rating for increased feed-in capacity:
If the supply air temperature drops below a value, it is possible to
feed this power as the maximum.