Protect 3.33
Protect 3.33: Online UPS system for datacenters a nd internet nodes
MODEL 3.33-10 3.33-20 3.33-30 3.33-40 3.33-60 3.33-80 3.33-100 3.33-120
Type power (at cos j 0.8 lag) in kVA
10 20 30 40 60 80 100 120
RECTIFIER UNIT
Input nominal voltage 3 x 400 V
operating range (min./max. ) 340 V 460 V
Frequency 45 66 Hz
Input current in A at nominal load 17 33 50 66 98 130 163 195
Input current in A at nominal load
+ battery charging
21 41 62 82 123 164 205 246
Charging characteristic to IEC 478-10 IU
Nominal DC voltage 384 V
Max. charging voltage 461 V
Total harmonic distortion
- Standard
- Optional
6 pulse
Filter
6 pulse
Filter
6 pulse
Filter
6 pulse
Filter
6 pulse
Filter
6 pulse
12 pulse
6 pulse
12 pulse
6 pulse
12 pulse
INVERTER UNIT
Nominal DC input min./max. 307 V / 461 V
Nominal AC voltage 3 x 400 V
Adjustable min./max. 380 V / 415 V
Static response < ±1 %
Dynamic response < ±5 %
Correction time 2 ms
Frequency 50/60 Hz
Frequency tolerance without mains ±0.1 %
Frequency synchronisation range ±1 %
Power factor range cos j cap-1-ind
Output phase current in A 14 29 43 58 87 116 145 173
Voltage wave form sinus
Voltage distortion 3 %
Crest factor 3 : 1
Overload response 1 min. 150 %
Overload response 10 min. 125 %
Short circuit response of I
nom
typical
300 %
STATIC BYPASS SWITCH
AC voltage min./nominal/max. 3 x 380 V / 400 V / 415 V
Frequency 50/60 Hz
Nominal power in kVA 10 20 30 40 60 80 100 120
Overload 500 %
GENERAL DATA
Efficiency total up to 94 %
Eco px (option) up to 98 %
Noise level depending on type < 55–65 dB(A)
EMC compatibility acc. EN 60040-2 C 2
Air cooling with redundant
and monitored fans
Yes
Operating temperature range min./max. –5° C/+40° C
Storage temperature range min./max. –30° C/+75° C
Installation height NN 1000 m
Protection degree acc. IEC 529 / EN 60529 IP20
Equipment colour RAL 7035
WEIGHTS AND DIMENSIONS
Height standard UPS (mm) 1710 1710 1710 1710 1710 1710 1710 1710
Height with max. options (mm) 1815 1815 1815 1815 1815 1815 1815 1815
Width (mm) 600 600 600 600 750 1200 1200 1200
Depth (mm) 735 735 735 735 735 735 735 735
Weight (kg) 350 370 450 470 550 800 900 900