Protect B. PRO
Protect B. PRO: Efcient protection with innovative
features for server and networks.
rotatable display device stands
Classication VI SS 211 acc. to IEC 62040-3 B. 750 PRO B. 1000 PRO B. 1400 PRO B. 1800 PRO B. 2300 PRO B. 3000 PRO
Type power 750 VA 1000 VA 1400 VA 1800 VA 2300 VA 3000 VA
675 W 900 W 1260 W 1620 W 2070 W 2700 W
Part number 600 000 8422 600 000 8424 600 000 8426
600 000 8428
600 000 8429 (BP)
600 000 8431 600 000 8432
UPS INPUT
Input voltage 220 Vac / 230 Vac / 240 Vac
Input voltage range without battery mode 182 Vac to 280 Vac
Frequency (auto selection) 50 Hz / 60 Hz ± 5Hz
Current consumption (max.) 3.6 A 4.8 A 6.7 A 9.8 A 11 A 14.5 A
UPS OUTPUT
Rated output voltage/AVR-technology 220 Vac / 230 Vac (Voreinstellung) / 240 Vac ± 10% (± 3% free running)
Frequency in battery mode 50 Hz / 60 Hz ± 1Hz
Output current (on 230Vac) 3.2 A 4.3 A 6.1 A 7.8 A 10 A 13 A
Transfer time at mains outage 2-6 ms (typical), 8 ms max.
Voltage waveform sinusoidal
Overload response (VI operation) < 120% for 5min. / 120-150% for 10s / >150% for 1s
Overload response (battery operation) < 110% for 1min. / 110-150% for 10s / 150-200% for 500ms
BATTERY
Type sealed, maintenance free, hot swappable
integrated yes yes yes no (external) yes yes
Rated voltage 24 Vdc 48 Vdc 72 Vdc
Battery management
temperature compensated with overload and deep discharge protection;
automatic battery test; batterypack detection
Autonomy time in min. (full/half load, cos phi=0.9lag.) 4,5 / 10,5 3,5 / 9,5 5,5 / 13,5
10 / 28 (1xBP)
26 / 62 (2xBP)
44 / 100 (3xBP)
4 / 14 4 / 11
Charging time (to 90% of rated capacity) 6h
COMMUNICATION
User interface LCD display with digital indication of UPS relevant values
Interface
RS232 & USB (with status notcation and UPS gures), additional communication slot in parallel mode
(SNMP/relay card); input contact for emergency power off
Shutdown software (on CD) 5 network licenses for all common OS (e.g. Windows, Linux, Mac)
Failure indicators (acoustical/optical)
3 LED indicators show UPS status, detailed indication via LCD display (mains failure, overload,
battery discharge, battery replace, fan failure)
GENERAL DATA
Efciency (in ECO mode) > 97%
(at whole AVR range) > 90 %
Audible noise at 1 m distance (max.) ≤ 45 dB (A) ≤ 55 dB(A)
Ditto at ECO mode and max. 70% load ≤ 40 dB (A) ≤ 45 dB(A)
Operating temperature range 0° bis +40°C
Storage temperature range -20° bis +50°C
EMC conformity
EN 62040-2 Class C1, EN 61000-3-2, EN 61000-3-3
Product safety EN 62040-1
Data lines protection
RJ11 (Phone, Fax, Modem) / RJ45 (Ethernet 10 Mbit/s / 100 Mbit/s)
Humidity 0 - 90% (non condensing)
Installation height / transportation operation up to 1000m at full load / air freight up to 10600 m
Mains input IEC 320 C14 IEC 320 C20
Number of outlets / of them controllable 8 / 4 7 / 3
via connectors 8 x IEC320 C13 6 x IEC320 C13
1 x IEC320 C19
Equipment colour black metal case / silver front
Size approx. W x H x D [mm] 440 (19“) x 88 (2 U) x 420 440 (19“) x 88 (2 U) x 520 440 (19“) x 88 (2 U)x 640
Net weight approx. [kg] 14,6 15,1 21,8 14,4 / 29,5 (BP) 29 29,5
Shipment mains input cord (1 x EU, 1 x UK)
Certication CE