AEG 6000003918+6000004095 Datasheet Page 39

  • Download
  • Add to my manuals
  • Print
  • Page
    / 52
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 38
39
Protect 3.M 2.0
Type power
80 kVA 120 kVA
64 KW 96 KW
Max. modules per rack 4 6
UPS INPUT
Input voltage 400/230Vac
Frequency 50/60Hz (Auto-Selectable)
Frequency range +/-5 Hz
Power factor > 0.99 (Full Load)
THD (i) <5%
UPS OUTPUT
Rated output voltage 400/230Vac
Frequency 50/60Hz +/-0,05%
THD (v) 3%
Transfer time at mains outage 0 ms (zero transfer)
Voltage waveform sinusoidal
Overload response (online mode)
<125% for 10 min.
<150% for 1 min
>150% for 0,3 sec
Crest factor 2,5 : 1
BATTERY
Nominal voltage ± 240 Vdc
Autonomy time
Free to choose runtime extension with
additional external battery
Overload/deep discharge protection yes
COMMUNICATION
Interfaces
RS232/RS485 for status and measurement values, communication slot
(for pot.-free contacts and SNMP adapter)
Failure indicators (acoustic/optical)
LCD with digital information of input and output parameters (voltage, frequency, power etc.) battery
parameter etc., LED for status and main failures
GENERAL DATA
Efficiency (total)
< 95% (< 98% in ECO Mode)
Audible noise (1 m distance)
64 to 69 dBA (depends on load)
Operating temperature range
0 – 40 °C
EMC conformity EN62040-2 Class C3, EN 61000-6-2, EN 61000-6-4
Product safety EN62040-1
Humidity
<90%
Installation height
up to 3000 m at nominal load
Equipment colour
RAL 7035
WEIGHTS AND DIMENSIONS
Weight approx. (module)
30 kg
(Empty rack)
139 kg 204 kg
(with maximum modules)
259 kg 384 kg
Size approx. W x H x D (mm)
520 x 1165 x 910 520 x 1665 x 975
Classification VFI SS 111
acc. to IEC 62040-3
Protect 3.M 80 Protect 3.M 120
operating buttons ON / OFF
EPO
UPS status LEDs:
normal
battery
bypass
failure
Display Protect 3.M
Protect 3.M 2.0: Modular UPS system for medium
-sized datacenters
Page view 38
1 2 ... 34 35 36 37 38 39 40 41 42 43 44 ... 51 52

Comments to this Manuals

No comments