AEG 6000008432 Operations Instructions Page 34

  • Download
  • Add to my manuals
  • Print
  • Page
    / 52
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 33
16
Protect 1.M
34
Protect 1.M: Modular high performance UPS system
Reliability
r High power reserves max. 24 kVA total
output
r High safety reserves n+x technology
r Integrated static bypass switch
r 3 phase or 1 phase connection of the
complete system; 1 phase output
r High autonomy time during power failure
r Manufacturer independent standard
batteries
r Intelligent battery management
r Hot-swappable - easy to exchange modules
r Module design in slide-in type in the
compact tower
r Communication module with LCD display,
Dual monitoring interface with extension
slot
r Software “CompuWatch“ on CD
Advantages
of n + x technology
r higher reliability
r easy to increase overall capacity
r modules hot-swapable
(without any interruption)
OYUFDIOPMPHZr3FEVOEBODZMFWFM
QUANTITY OF UPS MODULES
Load 1 module 2 modules 3 modules 4 modules 5 modules 6 modules
4 kVA no n+1 n+2 n+3 n+4 n+5
redundancy (4 kVA) (8 kVA) (12 kVA) (16 kVA) (20 kVA)
8 kVA no n+1 n+2 n+3 n+4
redundancy (4 kVA) (8 kVA) (12 kVA) (16 kVA)
12 kVA no n+1 n+2 n+3
redundancy (4 kVA) (8 kVA) (12 kVA)
16 kVA no n+1 n+2
redundancy (4 kVA) (8 kVA)
20 kVA no n+1
redundancy (4 kVA)
24 kVA no
redundancy
ALLOCATION OF THE BATTERY CABINETS AVAILABLE EX STOCK - IN PROTECT 1.M CONFIGURATION
15 min. 20 min. 30 min. 40 min. 60 min. 75 min. 90 min.
4 kVA – – – – – – – – – 1 x 1.M BP28 1 x 1.M BP42 – – – 1 x 1.M BP56
8 kVA 1 x 1.M BP28 – – – 1 x 1.M BP42 1 x 1.M BP56 1 x 1.M BP84 2 x 1.M BP65 1 x 1.M BP84
1 x 1.M BP42
12 kVA 1 x 1.M BP42 1 x 1.M BP65 – – – 1 x 1.M BP84 2 x 1.M BP65 – – – 3 x 1.M BP65
16 kVA 1 x 1.M BP56 – – – 1 x 1.M BP84 1 x 1.M BP84 2 x 1.M BP84 3 x 1.M BP65 4 x 1.M BP65
1 x 1.M BP42
20 kVA – – – 1 x 1.M BP84 1 x 1.M BP84 3 x 1.M BP65 2 x 1.M BP84 4 x 1.M BP65 5 x 1.M BP65
1 x 1.M BP42 1 x 1.M BP42
24 kVA 1x 1.M BP84 2 x 1.M BP65 1 x 1.M BP84 2 x 1.M BP84 4 x 1.M BP65 5 x 1.M BP65 6 x 1.M BP65
1 x 1.M BP42
„Dual-Monitoring“-Interface
Expansions-Slot
RS485
RS485
RS232
RS485
Expansion slot for
r relaycard with potential-free contacts
r SNMP and SNMPpro cards with connector
for remote control and sensors
Front view
Other designs are available on request.
Rear view
VFI
Page view 33