Protect 1.
Rear view Protect 1.200
parallel port
manual bypass switch
connection terminal cover
input fuse
RS232 communication port
fans
expansion slot for
communication cards
Protect 1. in parallel operation
Parallel Panel/Manual Bypass
plus UPS-Distribution
LV-Distribution
UPS-Input
r True online UPS including static bypass
(double-conversion VFI-technology)
r Power range 10,15, 20 kVA, space-saving
design n + x technology (DSP controlled)
to increase output power and/or for
redundancy
r State-of-the-art: High reliability and
efficiency by digital signal processing
(DSP), CAN bus system, and high frequency
IGBT technology.
r Uses battery systems with up to ten years
battery service life, according to EUROBAT
r Communication via RS232, expansion slot
for e.g. relaycard and SNMP
r 24 months warranty with pre-exchange
service
r Free 36 months warranty on UPS and
battery with advanced replacement service
(registration required)
“Plug & play” connection via a
battery connection cable which is
protected against polarity reversal
Ready-for-connection battery
cabinets, preassembled
Service life of the integrated
batteries: 10-12 years according
to EUROBAT
}
}
Coupled Autonomy time (full load/half load) [min.]
battery cabinets Protect 1.100 Protect 1.150 Protect 1.200
1 x Protect 1.100 BP 16/42 - -
2 x Protect 1.100 BP 42/97 - -
3 x Protect 1.100 BP 60/134 - -
1 x Protect 1. BP 20 19/47 10/29 6/19
2 x Protect 1. BP 20 47/103 29/68 19/47
3 x Protect 1. BP 20 78/177 47/103 34/62
4 x Protect 1. BP 20 103/243 68/153 47/103
5 x Protect 1. BP 20 138/312 85/202 63/138
Protect 1: Online UPS systems for networks and
Reliability
VFI
AUTONOMY TIME – BATTERY PACKS GENERALLY IN Protect 1. DESIGN