27UPS 20-30 kVA, 230 V 50/60 Hz output
Users Guide
1026743
Revision B
The UPS supports two serial communication devices according to the table below.
Independent Multiplexed
Configuration XSlot-1 XSlot-2 Std. RS-232 port
Default #1 Any XSlot Module Any XSlot Module Not in use
Default #2 Any XSlot Module Relay Module Available
Default #3 Any XSlot Module Not in use Available
Default #4 Any XSlot Module Hot Sync card Available
Table 3 Typical XSlot configurations for UPS communication.
Web/SNMP Module (optional)
The module supports HTTP and SNMP compliant remote monitoring and shutdown for
the protected computer systems. It can be connected to a twisted-pair Ethernet network
(10/100BaseT) using an RJ45 connector.
The Web/SNMP module has a build-in switching hub that allows three (3) additional network
devices to be connected to the network without the requirement of additional network drops.
In addition, an Environmental Monitoring Probe (EMP) can be requested from the UPS
manufacturer to obtain humidity, temperature and two relay inputs. It is connected to the
communication port of the Web/SNMP module as option.
Figure 13 ConnectUPS-X Web/SNMP Module and Environmental Monitoring Probe (EMP).
AS/400 Relay Module (optional)
The Relay Module provides potential free relay interface for AS/400 connected computers and
industrial applications. The relay interface supports both 15-pin D-sub connector and terminal
block connections up to four (4) potential free relays.
The relay contacts are rated for 1 A, 30 Vac or 200 mA, 60 Vdc, and they have a galvanic
isolation from the other circuits of the UPS unit.