10 Troubleshooting and Fault
Rectification
If error messages are displayed, please refer to the following
table in order to localise the fault that has occurred and to find
information about what measures to take to rectify the fault. If
you cannot resolve the problem(s), please contact the Service
Center (see page
5 "Hotline").
1. Check whether the UPS connection, and specifically the
mains connection, has been made correctly.
2. Check whether the input voltage has been applied correctly
(check for phase(s) connected to the neutral conductor and for
the phase sequence, if appropriate).
3. Check the connection of the battery system (polarity and nominal
voltage).
4. Make a note of the status of the unit when the fault occurred
(LC display) and the error code number that is displayed.
Overview of fault messages
PROBLEM POSSIBLE CAUSE SOLUTION
Overload in normal / bypass or battery
operation
Reduce the load.
Applied mains not in tolerance range
Check whether input cabling and UPS
input voltage are normal.
Error/fault LED lights up, periodic
warning signals
Battery system faulty / not connected
Check whether the voltage of the battery
system is correct and that the battery fuse-
switch disconnector is made.
Error/fault LED lights up,
continuous warning signal
UPS fault
Battery system aged/reached end of useful
life
Battery discharge time is 1/3 shorter
compared to 1st
time
Charging error
Contact the Customer Service Center.
LC display dark or faulty
LCD displays that data cable is not
attached correctly (?)
Make sure that the communication module
has been installed correctly; check both
plugs of the ribbon cable for the LC
display are connected correctly.
CompuWatch or SNMP(pro) do
not detect the PROTECT 1.M >>
No communication
Software status of CompuWatch or
firmware of SNMP(pro) card outmoded;
error in computer configuration
Download the latest software /
firmware from the AEG homepage.
Check the communication cable.
The LC display does not display
any inserted UPS modules
Modules, housing or units are not
connected correctly.
Pull the module out and re-insert it into the
slot (click!) or use a different slot.
Mains power is connected but the
UPS does not start operating.
Mains not in tolerance; phase loss or
possible phase sequence error; cover
removed from bypass switch.
Check the mains voltage and UPS
connection; replace cover of bypass
switch if removed.