AEG 61000M Operations Instructions Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 56
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
11
176 VAC – 264 VAC ±3%
(Bypass)
Frequency 50 Hz / 60 Hz
(Automatic detection)
Frequency tolerance range ±4 Hz
Current consumption at full load (max.)
PROTECT 1.M (system) 44 A (3ph~) or 132 A (1ph~) / 155
A (Bypass)
PROTECT 1.040 (module) 7.3 A (3ph~) or 22 A (1ph~)
System disturbance factor λ 0.98
UPS output
Nominal voltage output 220 / 230 / 240 Vac ±2%
(configuration via "CompuWatch"
software)
Nominal frequency 50 Hz / 60 Hz ±0.2 Hz (dependent
on mains frequency)
Type of voltage Sine, distortion
< 3% THD (linear load)
< 6% THD (non-linear load)
Crest factor 3:1
Overload behaviour Up to 105% continuous;
with mains supply > 105% – < 130% for 30s
130% for 2
s
Following this, automatic,
uninterrupted switchover to
integrated bypass (SBS).
Switch-off after 1 min. if overload
continues to be present (switch
back if overload decreases = load
< 90%)
Overload behaviour with Up to 105% continuous;
battery operation > 105% – < 130% for 30s
130% for 2
s
Short-circuit behaviour 3 x I
N
for 100 ms
Page view 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 55 56

Comments to this Manuals

No comments