AEG 800 KVA User Manual Page 4

  • Download
  • Add to my manuals
  • Print
  • Page
    / 4
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 3
AEGPS - Fluxpower HPS - EN - 08/2013 V1 - Technical data in this document does not contain any binding guarantees or warranties. Content only serves for information purposes and can be modified at any time. We will make binding
commitments only upon receipt of concrete enquiries and customer notification of the relevant conditions. Due to the non-binding nature of these terms, we assume liability neither for the accuracy nor completeness of the data provided here.
AEG is a registered trademark used under license from AB Electrolux.
AEG Power Solutions
Approach your local AEG Power Solutions
representative for further support.
Contact details can be found on:
www.aegps.com
FLUXPOWER
HPS
SPECIFICATION
Model (kVA) 400 500 600 800
Capacity rating (kVA) 400 500 600 800
Dimensions WxHxD (mm) 1990x1920x990 2440x2020x990 2440x2020x990 3640x1920x990
Weight (kg) 1820 2220 2400 3600
Input/output connection Hard wired (dual input)
Battery External, 300-312 cells
INPUT
Nominal voltage 220/380, 230/400, 240/415 VAC single / 3-phase
Voltage range -20%, +15% at 400 V nominal
Frequency 50/60 Hz (45–65 Hz)
Power factor 0.99
Current distortion (THDi) <3.5%
OUTPUT
Nominal voltage 220/380, 230/400, 240/415 V AC three phase
Frequency 50/60 Hz
Voltage regulation ±1% static; ±5% dynamic 100% load change
PF acceptable without de-rating Lagging to leading 0.9
Overload capacity 101 – 125% for 10 min (on-line), 126 – 150% for 1 min (on-line),
1000% for 1 cycle (bypass)
Efficiency; VFI, double-conversion ≤94.8 %
Efficiency; Wise ECO mode 95 – 98% (>98%)
OPTIONS
General 8 x parallel capacity/redundancy, sync control, isolation transformer, external
bypass, external battery cabinets, battery switch box, battery thermal probe,
transformers/autotransformers for voltage adaption, top cable entry
USER INTERFACE
Front panel Graphical LCD display, mimic with LED’s and keyboard
Standard communication ports RS232 serial, USB, Remote Emergency Power Off input, Battery Switch status
monitoring, External Manual Bypass status monitoring, Diesel Mode
Optional communication Web/SNMP, ModBus, Relay, Modem cards; Remote panel;
Monitoring, Managing and shutdown software
ENVIRONMENTAL
Operating temperature 0°C – +40°C
Storage temperature -10°C – +70°C
Altitude <1000 m; 1 % power derating each 100 m above, max. 2000 m
Audible noise at 1 meter dB(A) <60
STANDARDS AND CERTIFICATION
Marking and certification CE, GOST, ECA ETL
Safety IEC EN 62040-1
EMC IEC EN 62040-2
Test and Performance IEC EN 62040-3
Quality, environment, health and safety ISO9001:2008, ISO 14001:2004, BS OHSAS 18001:2007