CG–2 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE
COMMUNICATIONS GUIDE
is important in RS485 communications. Each '+' terminal of every device must be
connected together for the system to operate. See Section 2.1.3 in the 239 Instruction
Manual for details on correct serial port wiring.
CG.1.3 Data Frame Format / Data Rate
One data frame of an asynchronous transmission to or from a 239 consists of 1 start
bit, 8 data bits, and 1 stop bit. This produces a 10 bit data frame. This is important for
transmission through modems at high bit rates (11 bit data frames are not supported
by Hayes modems at bit rates of greater than 300 bps).
Modbus protocol can be implemented at any standard communication speed. The
239 supports operation at 1200, 2400, 4800, 9600, and 19200 baud.