AEG 239 D User Manual Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 58
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
COMMUNICATIONS GUIDE
239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–7
FUNCTION CODE - 1 byte 03 read registers
BYTE COUNT - 1 byte 06 3 registers = 6 bytes
DATA 1 - 2 byte 00 00 bit set corresponding to
command 13
DATA 2 - 2 bytes 00 00 value in address 006C
DATA 3 - 2 bytes 00 00 value in address 006D
CRC - 2 bytes EC B5 CRC calculated by slave
CG.3.2 05: Execute Operation
Modbus Implementation: Force Single Coil
239 Implementation: Execute Operation
This function code allows the master to request a 239 to perform specific command
operations. The command numbers listed in the Commands area of the memory map
correspond to operation code for function code 05.
The operation commands can also be initiated by writing to the Commands area of
the memory map using function code 16. Refer to Section CG.4: 16: Performing
Commands on page –12 for complete details.
MESSAGE FORMAT AND EXAMPLE
Reset 239 (operation code 1).
Master Transmission Bytes Example (hex)
SLAVE ADDRESS - 1 byte 11 message for slave 11
FUNCTION CODE - 1 byte 05 execute operation
OPERATION CODE - 2 bytes 00 01 reset command
(operation code 1)
CODE VALUE - 2 bytes FF 00 perform function
CRC - 2 bytes DF 6A CRC calculated by the
master
Slave Response Bytes Example (hex)
SLAVE ADDRESS - 1 byte 11 message from slave 11
FUNCTION CODE - 1 byte 05 execute operation
OPERATION CODE - 2 bytes 00 01 reset command
(operation code 1)
CODE VALUE - 2 bytes FF 00 perform function
CRC - 2 bytes DF 6A CRC calculated by slave
CG.3.3 06: Store Single Setpoint
Modbus Implementation: Preset Single Register
239 Implementation: Store Single Setpoint
Page view 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 57 58

Comments to this Manuals

No comments