COMMUNICATIONS GUIDE
239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–25
103E Reserved
103F Reserved
1040 ALARM
RELAY
Alarm Operation 0-1 1 --- F16 0 = NON-
FAILSAFE
1041 Alarm Activation 0-1 1 --- F17 0 =
UNLATCHED
1042 Reserved
1043 Reserved
1044 Reserved
1045 Reserved
1046 Reserved
1047 Reserved
1048 AUXILIARY
RELAY
Auxiliary Operation 0-1 1 --- F16 0 = NON-
FAILSAFE
1049 Auxiliary Activation 0-1 1 --- F17 0 =
UNLATCHED
104A Auxiliary Function 0-2 1 --- F18 0 = NORMAL
104B Reserved
104C Reserved
104D Reserved
104E Reserved
104F Reserved
1050 PHASE
TIMED O/L
Phase Timed O/L Curve No 1-15 1 --- F1 4
1051 Phase Timed O/L Lockout Time 1-5000 1 min F1 30 min
1052 Overload Level to Calculate Trip
Time
101-2000 1 0.01xFLC F1 200 = 2.00
xFLC
1053 Auto Reset Overload Trips 0-1 1 --- F14 0 = NO
1054 Reserved
1055 Reserved
1056 Reserved
1057 Reserved
1058 PHASE
S/C
Phase S/C Trip 0-3 1 --- F19 0 = OFF
1059 Phase S/C Pickup 10-110 1 0.1 xCT F1 100 = 10.0 xCT
105A Phase S/C Delay 0-60000 10 ms
F1
0 ms
105B Reserved
105C Reserved
Table CG–1: 239 Memory Map (Sheet 11 of 21)
REG
ADDR
(HEX)
GROUP DESCRIPTION REGISTER
VALUE
RANGE
STEP
VALUE
UNITS &
SCALE
FORMAT FACTORY
DEFAULT
VALUE
(CONVERTED)
1, 2, 3,
*
,
**
,
***
,
****
,
†, ‡
See page 36 for explanation of Table notes.