GE Consumer & IndustrialMultilinLISTED52TLIND.CONT. EQ.E83849239MOTOR PROTECTION RELAYCommunications GuideFirmware Revision: 2.7x239PC Software: 2
CG–6 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDECG.3 239 Supported Modbus FunctionsThe following functions are supported b
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–7FUNCTION CODE - 1 byte 03 read registersBYTE COUNT - 1 byte 06 3 registers
CG–8 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDEThis command allows the master to store a single setpoint into the memory
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–9MESSAGE FORMAT AND EXAMPLERequest status from slave 11.Master Transmission
CG–10 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDEMESSAGE FORMAT AND EXAMPLELoopback test from slave 11.Master Transmission
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–11DATA 1 - 2 bytes 00 96 data for address 1028DATA 2 - 2 bytes 00 96 data f
CG–12 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDECG.4 16: Performing CommandsSome PLCs may not support execution of comman
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–13CG.5 Error ResponsesWhen a 239 detects an error other than a CRC error, a
CG–14 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDECG.6 Memory Map InformationThe data stored in the 239 is grouped as Setpo
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–15CG.6.2 239 Memory MapTable CG–1: 239 Memory Map (Sheet 1 of 21)REG ADDR (
© 2007 GE Multilin Incorporated. All rights reserved.GE Multilin 239 Motor Protection Relay Communications Guide for revision 2.7x.239 Motor Protectio
CG–16 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE002F Reserved0030 Calibration Day --- --- --- F1 day of calibration0031 C
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–170090 Reserved↓↓00FF ReservedUser Definable Register (Input Registers) A
CG–18 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE0188 Register address for User Definable Data 0008† 1 --- F1 00189 Regist
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–190216 Pre-Trip RTD 1 Temp. (RTD Option)--- --- °C F2**** N/A0217 Pre-Trip
CG–20 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE0233 Reserved0234 Reserved0235 Reserved0236 Reserved0237 Reserved023
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–210250 DEBUG ADC Reference --- --- --- F1 N/A0251 DATA Thermistor Reading -
CG–22 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE026C Message Buffer characters 25 and 26--- --- ASCII F8 N/A026D Message
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–23Setpoint Values (Holding Registers) Addresses – 1000 to 11EF1000 PREFEREN
CG–24 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE101E Reserved101F Reserved1020 CTINPUTSPhase CT Primary 0-1500 5 A F1 *
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–25103E Reserved103F Reserved1040 ALARMRELAYAlarm Operation 0-1 1 --- F16
TABLE OF CONTENTS239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE TOC–ITable of ContentsCOMMUNICATIONS ...
CG–26 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE105D Reserved105E Reserved105F Reserved1060 IMMEDIATEOVERLOADImmediate
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–27107D Reserved107E Reserved107F Reserved1080 HOT MOTOR % Thermal Capaci
CG–28 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE109A Thermistor Cold Resistance 1-300 1 0.1 kΩ F1 3 = 0.3 kΩ109B Thermist
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–2910B8 RTD SENSOR RTD Sensor Fail Alarm (RTD Option)0-1 1 --- F20 0 = OFF10
CG–30 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE10D8 ANALOGSIMULATION Simulation (AN Option) 0-1 1 --- F20 0 = OFF10D9 Fo
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–3110F8 FLASHMESSAGEFlash message characters 1 and 232-127 1 ASCII F8 "
CG–32 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE1110 PROGRAMMA-BLEMESSAGEProgrammable message characters 1 & 232-127
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–331128 SWITCHSIMULATIONSimulation 0-1 1 --- F20 0 = OFF1129 Emergency Resta
CG–34 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE1190 OPTIONSWITCH 1Option Switch 1 characters 1 and 232-127 1 ASCII F8 &
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–3511B6 Option Switch 2 characters 13 and 1432-127 1 ASCII F8 "H "
TOC–II 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDETABLE OF CONTENTS
CG–36 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDEMEMORY MAP TABLE NOTESNotes: * = Minimum Setpoint value represents “OFF”
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–37 0 = No Trip --- 1 = Overload --- 2 = Short Circuit --- 3 = Mechanical Ja
CG–38 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE 0 = No Trip --- 1 = Overload --- 2 = Short Circuit --- 3 = Mechanical Ja
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–39 FB02 = VALUE DOWN ---F8 TWO ASCII CHARACTERS FFFF 32-127 = ASCII Charact
CG–40 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDEF14 UNSIGNED INTEGER - YES / NO FFFF 0 = No --- 1 = Yes ---F15 UNSIGNED I
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–41 0 = Off --- 1 = Alarm --- 2 = Auxiliary --- 3 = Trip --- 4 = Alarm &
CG–42 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE 4 = Alternate Setpoints --- 5 = Disable Starts ---F27 COMMAND FFFF 1 = R
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–43 0 = Normal --- 1 = Trip --- 2 = Alarm --- 3 = Trip and Alarm --- 4 = Rel
CG–44 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDEF36 SIMULATED SWITCH STATE FFFF 0 = OPEN --- 1 = CLOSED ---F38 GROUND TRI
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–45F45 UNSIGNED LONG INTEGER(NUMERICAL DATA)FFFFFFFFF100 SWITCH INPUT STATUS
239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–1239 Motor Protection RelayCommunications GuideGE Consumer & IndustrialMultilinTRIPALARMAUXIL
CG–46 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE Not Used 0200 Not Used 0400 Not Used 0800 Not Used 1000 Not Used 2000 No
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–47 Short Circuit 0020 Stator RTD (RTD Option) 0040 Bearing RTD (RTD Option)
CG–48 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDEF105 INTERNAL FAULT ERROR CODE FFFF ADC Reference Out of Range 0001 HC705
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–49 Not Used 0800 Not Used 1000 Not Used 2000 Not Used 4000 Not Used 8000F10
CG–50 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE Communicate 0020 Not Used 0040 Not Used 0080 Not Used 0100 Not Used 0200
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–51 2 = 3rd Group --- 3 = 4th Group ---F114 Ground Current Scale Factor FFFF
CG–52 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDE
INDEX 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG-INDEX–1IndexIndexABCCOMMUNICATIONSdata format ...
CG-INDEX–2 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDEINDEXfunction code 08 – loopback test ...
CG–2 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDEis important in RS485 communications. Each '+' terminal of every
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–3CG.2 Data Packet FormatA complete request/response sequence consists of th
CG–4 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE COMMUNICATIONS GUIDEnumber. This number is first shifted left 16 bits and then divided by a ch
COMMUNICATIONS GUIDE 239 MOTOR PROTECTION RELAY – COMMUNICATIONS GUIDE CG–58. is j = 8? No: go to 5.Yes: go to 9.9. i+1 --> i10. is i = N? No: go