Table 2 Loadable DX Upgrades
Loadable
Part
ICMP I DRUM
MTRM
EARS
EUCA
HLTH
MAP3
FNXX
CALL
Disk Media
P190 Tape
Disk Media
PI 90 Tape
Disk Media
SW-APS&SDA
SW-AP98-STA
SW-MRTM-1 DA
SW-MRTM-1 TA
SW-APSD-EDA
SW-EUCA-D8L
SW-HLTH-D8L
SW-APPL-MAP
SW-AP98-GDA
SW-AP98-CXA
- -
Hot standby is supported with an AS-S911-801 module with the following limits:
HSBY data transfers are limited to 9999 registers, including up to 1000 input
registers (3x references), 8192 discrete outputs (Ox references), and 8192
discrete inputs (1 x references)
The Hot standby Loadable must be Rev. C or greater
The Remote I/O processor is an S908-1 xx with an E908-131 Executive PROM
1006 or higher. Both RIOPs in the hot standby system must have identical PROM
revision levels.
o The PC-L984-785, when used as a PC-0984-785 replacement, retains identi-
cal functionality to the PC-0984-785.
Reference Documents
GM-0984-SYS
GM-0984-501
GM-MSFT-001
PI-MBUS-300
GM-MBPL-004
GM-MBPL-001
Modicon 984 Programmable Controller S,ystems Manual
Modicon 6801685 780/785/785L
System Planning and Installation Guide
Modicon Modsoft Programmer User Manual
Rev. C Modicon Modbus Protocol Reference Guide
X85 Controller Modbus Plus installation
Modbus System Planing
4
Introduction
GM-L984-785 Chapter 1