Input set points
The Power Controller Thyro-A is equipped with two input set points which are isola-
ted from the mains.
• Set point 1 analog (X2.4 – X2.3 ground)
• Set point 2 system interface
The analog input can be adapted to the various process controllers by means of
the set point and live zero set point switches. The following signal ranges can be
set:
0(4)-20mA (R
i
= ca. 250), 0-5V (R
i
= ca. 44k), 0-10V (R
i
= ca. 88k).
Within the stated input ranges these values with the control characteristic may be
adjusted to any common signal characteristic.
+5V supply voltage can be taken for a set point potentiometer from terminal X2.8
(5kR
Poti
10k).
The effective set point is the total set point. It is made by adding the two set points. It
is either the analog set point or the bus set point. If the bus module is connected and
in operation, the bus set point is effective.
If the bus module or bus (e.g. Profibus-DP) is interrupted, the controller automatically
switches to the analog set point.
Fig. 2 Set point inputs and total set point